IOWA CITY MODERATED FORSALE NEWSGROUP   >   Industrial Equipment   >   Light Industrial   >   Flow switch....air, water + more

Flow switch....air, water + more


This is a used FCI 12-64B-AOB1. It was removed from working service after a short time in an air duct being used to prove air flow.
I have three of these available. This product is used and should be thoroughly tested by qualified personnel before being put in service.
Detaills....cut and paste this link in your browser: http:// /Industrial/Products/FlowSwitches/prod1264B.asp
FCI's first and most widely used flow switch monitor, the 12-64B BASIC insertion type flow switch provides low flow detection over a wide flow range. Any type of external control system can be actuated from either the normally open or closed output contacts of the instrument's on-board control circuit board DPDT relay.
The flow sensing element of the instrument and its modular control circuit are mounted in a rugged aluminum enclosure that is Factory Mutual, CSA, CENELEC and CE Mark approved for hazardous location service.
The wetted surfaces of the sensing element are 316 stainless steel with nickel-braze providing resistance to most liquid, gaseous and particulate media.
0.015 to 0.5 fps [0.005 to 0.15 mps]
0.01 to 2.0 fps [0.003 to 0.61 mps]
1.0 to 125 sfps [0.3 to 38 smps] at standard conditions of
70° F [21.1° C] and 14.7 psia [1.013 bar(g)].
Repeatability: 1% of full signal range at constant process conditions.
Response Time: As low as 10 seconds.
Enclosure: Epoxy coated aluminum enclosure is rated for hazardous location use (Class I and II, Division 1 and 2, Group B, C, D, E, F and G; and EEx d IIC) and resists the effect of weather and corrosion (NEMA and CSA Type 4X and equivalent to IP66).
Agency Approvals: FM, CSA, CENELEC and CE Mark.
Materials of Construction: All wetted surfaces 316 stainless steel with nickel braze per process specification AMS 4777.
Process Connection: 1 inch male NPT
Insertion Length: 1.2 or 2 inches [30 or 51 mm]
Operating Temperature: -100° to +350° F [-73° to +177° C]
Operating Pressure: To 3000 psig [207 bar(g)]
Operating Temperature: -40° to +140° F [-40° to +60° C]
Input Power: 115 ± 15 Vac, 230 ± 30 Vac (50/60 Hz), or 22 to 30 Vdc; 6 watts maximum.
Relay Contacts: DPDT rated 2 amps at 115 Vac and 24 Vdc, or 1 amp at 230 Vac.
Electrical Connection: 1 inch female NPT



Flow switch....air, water + more Flow switch....air, water + more